Highlights
The UPT210 with option "RGW" can be combined to the MFC150 Rogowski coil.
- Compact 6 DIN modules size
- High contrast LCD display
- True RMS measurement
- Active, reactive and apparent energy (4 counters)
- Neutral current measurement
- More than 35 electrical parameters measured and displayed (ENH version)
- Power and current demand calculation
- RS485 communication port
- Programmable transformer ratios
- Two digital outputs for energy pulsing
- Indication of phase sequence and wrong CT connection
- Up to 1% accuracy
The UPT210 with option "RGW" can be combined to the MFC150 Rogowski coil.
Applications
- Switchboards, gensets, motor control centers, etc.
- Replacement of electromechanical meters for household, industrial and commercial applications
- Power monitoring & control systems
- Individual machine load monitoring
- Capacitor bank operation supervision
- Remote metering and cost allocation
Main features
Measurements
Front panel display
Communication
Inputs & outputs
Advanced diagnostic functions
- Single phase and three-phase 3-wire or 4-wire unbalanced load operation.
- True RMS metering provides accurate measurement even for distorted waveform.
- More than 35 electrical parameters are measured. The basic version displays on the LCD the system values for a quick and easy check of the load conditions. The table on the right shows the measured parameters and the available options.
- Programmable 1A / 5A current full scale allows to fit the standard CTs.
- CT primary value is programmable up to 9999 to show the real energy consumption values
Front panel display
- High contrast LCD display.
- Two keys ensure the selection of the information on the LCD display and the instrument programming.
- Password protected setup and resetting operations.
Communication
- RS485 optoisolated communication port (option).
- Selectable MODBUS or A2 ASCII protocol. LONBUS protocol on request.
- Communication speed programmable up to 57600 bps (78 kbps in case of LONBUS).
Inputs & outputs
- Two digital optoisolated outputs for energy pulsing. The pulse value is programmable.
- On request input for Rogowski coils.
Advanced diagnostic functions
- Wrong current transformer polarity and phase sequence connection errors are indicated on the LCD display.
- Over / undervoltage, overcurrent and frequency out of range are detected to indicate the uncorrect working conditions.
- Pulse emission frequency too high or CT too high are checked to indicate programming mistakes.
Specifications
Power supply (1)
Rated voltage: powered from measuring inputs
Consumption: 0.8 VA max
Voltage inputs
Rated voltage: A) 3x230/400 VAC +15% -20% - 4 wires
B) 3x120/208 VAC +15% -20% - 4 wires
C) 3x400 VAC +15% -20% - 3 wires
D) 3x208à·230 VAC +15% -20% - 3 wires
E) 3x100à·120 VAC +15% -20% - 3 wires
Input impedance: ›1,3 MOhm
Burden: max 0,15 VA per phase
Frequency: 45 - 65 Hz
Current inputs
Rated current (Ib): 1 / 5 ARMS programmable
Min / max measurable current: 20 mA / 7 ARMS
Maximum overload: 10 ARMS continuous - 100 ARMS for 1 sec.
Input impedance: 0,02 Ohm approximately
Burden: max 0,5 VA per phase
Insulation voltage: 480 VAC max between phases
Rogowski input: 200à·49995 A on request
Typical accuracy
Voltage: ±0.3% reading ±0.05% full scale
Current: ±0.5% reading ±0.05% full scale
Active power: ±1% reading ±0.1% full scale (PF=1)
Power factor: ) 1.5% reading (0.5 inductive - 0.8 capacitive)
Active energy: 1% reading (0.5 inductive - 0.8 capacitive)
Frequency: ±0.05% reading ±2 digits from 45 to 65 Hz
Display and operating controls
Display: high contrast LCD display 43x19 mm
8 digits for energies and other parameters + symbols
Keypad: 2 push-buttons
Communication port (2)
Type: RS485 on request, optoisolated
Baud rate: 300 to 57600 bps
Protocols: A2 ASCII, MODBUS
Digital outputs
Type: 2 NPN or PNP optoisolated
(10à·50V-100mAAC-DC or 5à·50V-100mAAC-DC)
Environmental conditions
Operating temperature: from -15 °C to +60 °C
Storage temperature: from -25 °C to +75 °C
Relative humidity: 80% max. without condensation
Mechanical characteristics
Material: plastic enclosure - noryl UL94-V0
Protection degree: IP51 (front panel); IP20 (terminals)
Terminals: conductors 2,5 mm2
Size / weight: 106x90x57 mm, 6 DIN rail modules / 300gr
Standards compliance
Safety: 73/23/EEC and 93/68/EEC directives, EN61010.1 safety standard
EMC: 89/366/EEC directive and following modifications 93/31/EEC and 93/68/EEC, EN50081-2, EN50082-2, EN61326/A1
Rated voltage: powered from measuring inputs
Consumption: 0.8 VA max
Voltage inputs
Rated voltage: A) 3x230/400 VAC +15% -20% - 4 wires
B) 3x120/208 VAC +15% -20% - 4 wires
C) 3x400 VAC +15% -20% - 3 wires
D) 3x208à·230 VAC +15% -20% - 3 wires
E) 3x100à·120 VAC +15% -20% - 3 wires
Input impedance: ›1,3 MOhm
Burden: max 0,15 VA per phase
Frequency: 45 - 65 Hz
Current inputs
Rated current (Ib): 1 / 5 ARMS programmable
Min / max measurable current: 20 mA / 7 ARMS
Maximum overload: 10 ARMS continuous - 100 ARMS for 1 sec.
Input impedance: 0,02 Ohm approximately
Burden: max 0,5 VA per phase
Insulation voltage: 480 VAC max between phases
Rogowski input: 200à·49995 A on request
Typical accuracy
Voltage: ±0.3% reading ±0.05% full scale
Current: ±0.5% reading ±0.05% full scale
Active power: ±1% reading ±0.1% full scale (PF=1)
Power factor: ) 1.5% reading (0.5 inductive - 0.8 capacitive)
Active energy: 1% reading (0.5 inductive - 0.8 capacitive)
Frequency: ±0.05% reading ±2 digits from 45 to 65 Hz
Display and operating controls
Display: high contrast LCD display 43x19 mm
8 digits for energies and other parameters + symbols
Keypad: 2 push-buttons
Communication port (2)
Type: RS485 on request, optoisolated
Baud rate: 300 to 57600 bps
Protocols: A2 ASCII, MODBUS
Digital outputs
Type: 2 NPN or PNP optoisolated
(10à·50V-100mAAC-DC or 5à·50V-100mAAC-DC)
Environmental conditions
Operating temperature: from -15 °C to +60 °C
Storage temperature: from -25 °C to +75 °C
Relative humidity: 80% max. without condensation
Mechanical characteristics
Material: plastic enclosure - noryl UL94-V0
Protection degree: IP51 (front panel); IP20 (terminals)
Terminals: conductors 2,5 mm2
Size / weight: 106x90x57 mm, 6 DIN rail modules / 300gr
Standards compliance
Safety: 73/23/EEC and 93/68/EEC directives, EN61010.1 safety standard
EMC: 89/366/EEC directive and following modifications 93/31/EEC and 93/68/EEC, EN50081-2, EN50082-2, EN61326/A1
(1) The basic instrument is powered from L1, L2, L3 and N (4-wire version) or L1, L2, L3 (3-wire version). The presence of only one of the three phases
(4-wire version) or two phases (3-wire version) ensures the normal counting and displaying operations.
(2) The serial port is powered from L1 and N (4-wire version) or L1 and L2 (3-wire version). The communication function is ensured only if the L1 phase (or L1 and L2 for 3-wire) is present and within the specified range.
(2) The serial port is powered from L1 and N (4-wire version) or L1 and L2 (3-wire version). The communication function is ensured only if the L1 phase (or L1 and L2 for 3-wire) is present and within the specified range.